考虑气动阻尼格构式输电塔风振响应计算的有效方法
首发时间:2010-01-11
摘要:格构式输电塔兼有质轻、高柔和小阻尼特点,进行气动弹模型风动试验是更加准确研究其反应行为的必要条件,而气动弹模型与风场相互作用会产生气动阻尼力,为此计算风振响应的一般思路是需要首先对气动阻尼加以评估。本文提出了无需评估气动阻尼的“直接传递函数法”即可进行计算风振反应的新途径,并对该方法从物理角度加以解释。该方法物理概念清晰、理论合理可行,与传统方法是殊途同归,优点是不仅减少了对气动阻尼评估这一步骤,还最大限度避免了由于气动阻尼评估不准确可能会给计算结果带来的误差。
关键词: 输电塔 气动弹模型 风洞试验 气动阻尼 直接传递函数法
For information in English, please click here
A new effective approach to calculate wind-induced response of latticed transmission tower considering aerodymamic damping
Abstract:It is very necessary, in order to evaluate the wind-induced responses of latticed transmission towers more accurately, to conduct wind tunnel test of aeroelastic models because they are lightweight, very tall, flexible structures characterized by low damping. Interaction between aeroelastic model and wind field yields aerodymamic damping force. So, from the conventional perspective, evaluation of aerodymamic damping becomes the necessary step for the calculation of structural response. In this paper, a new approach called here DTF (Directly Transfer Function) method is presented and proposed to calculate the RMS structural displacement response. The new approach is reasonable and feasible and has explicit physical meaning. Comparing with conventional method, the advantage of the new approach is that it can avoid the process of evaluating aerodymamic damping ratio and so the possible calculation error production that is due to the inaccuracy of evaluating aerodymamic damping can also avoided.
Keywords: transmission tower aeroelastic model wind tunnel test aerodymamic damping direct transfer function method